Installing an above ground oil water separator is not a plug-and-play task. It requires careful site evaluation, proper foundation work, correct piping connections, and thorough commissioning. Each decision—from where the unit sits to how the discharge line slopes—affects separation efficiency, regulatory compliance, and long-term maintenance costs. Whether you are replacing an aging system or specifying a new unit for an industrial facility, the following installation tips will help you avoid common mistakes and get the system running correctly the first time.
Before any equipment arrives on site, conduct a thorough assessment of the installation area. This step determines whether your chosen location can support the separator's weight, drainage needs, and service access requirements.
The ideal location balances proximity to the water source with practical access for maintenance crews and vacuum trucks. Consider these factors:
Local, state, and federal regulations govern oil water separator discharge limits. Before installation, confirm the allowable oil and grease concentration for your jurisdiction—many municipalities set a limit of 100 mg/L or lower. You may also need a discharge permit or a pretreatment agreement. Overlooking this step can result in fines and forced system modifications after installation.
Working with an experienced manufacturer such as Zhengyuan Petrochemical can streamline this phase, as they often provide documentation and guidance tailored to regional compliance standards.

The foundation bears the full weight of the separator, the water inside it, and any associated piping and access structures. A poorly prepared base leads to settling, misalignment, and cracked tanks.
For most above ground units, a reinforced concrete pad is the standard choice. Key specifications include:
If a concrete pad is not feasible, a compacted gravel base with a geotextile liner can work for smaller units, but verify with the manufacturer before proceeding.
Once the foundation has cured, position the separator using a crane or forklift rated for the wet weight of the unit. Never attempt to move a partially filled separator. After placement, verify levelness in both directions using a spirit level or laser level.
If the unit is not level, the internal baffles and coalescing media will not function as designed. Water may short-circuit through the oil layer, and sludge may accumulate unevenly. Adjust the unit using stainless steel shims, then secure it to the pad with anchor bolts.

Piping is where many installations go wrong. Incorrect pipe sizing, inadequate slope, or improper venting can undermine even the best separator design.
The inlet line should deliver flow at a steady, controlled rate. Avoid high-velocity discharge that stirs up the contents. Install a flow diffuser or stilling chamber at the inlet if flow rates are variable or high. The pipe should slope toward the separator at a minimum of 1% (1/8 inch per foot) to prevent standing water in the line.
The outlet carries treated water to the discharge point. It must be sized to handle peak flow without backing up into the separator. A common mistake is undersizing the outlet pipe, which causes the unit to surcharge and reduces retention time. Slope the outlet line away from the separator at a minimum of 1% as well.
Proper venting prevents vacuum conditions and odor buildup. Install a vent pipe at the highest point of the separator, sized according to the manufacturer's recommendations. The vent should terminate outdoors, away from air intakes and occupied areas.
If your separator includes a pump, oil skimmer, or level sensors, the electrical work must comply with local codes. Use waterproof conduit and junction boxes rated for wet locations. Label all circuits clearly and provide a lockout/tagout point for maintenance. Test all alarms and sensors before filling the unit with water.

After mechanical and electrical installation, the system must be commissioned properly. Follow these steps:

Inspect the unit monthly and remove accumulated oil and sludge as needed. Most industrial facilities require professional cleaning every three to six months, depending on flow and oil load.
Yes, but indoor installation requires adequate ventilation, containment measures, and easy access for maintenance. Confirm that local fire and environmental codes permit indoor placement.
Sizing depends on peak flow rate, oil concentration, and retention time requirements. A qualified supplier can help you calculate the correct size based on your specific operating conditions.
Getting the installation right from the start saves time, money, and regulatory headaches. By following these guidelines and working with a reputable manufacturer, you can ensure your above ground oil water separator performs reliably for years.
Address: No. 8, Xinxin Road, Luoxin Industrial Park, Xin'an County, Luoyang, China